Criterion | Feature |
Dimensions W x L x H | (incl. interlinking block and connection technology) 50 mm x 107 mm x 70 mm |
Grid dimension | 50 mm |
Number of selectable analogue inputs/outputs | 4 |
Diagnosis | Wire break per channel Limit violation per channel Limit violation to NE43 per channel Short circuit/overload per channel parameterisation error Overflow/underflow |
Parameters configuring | Fail-safe mode per channel Data format Forcing per channel Limit monitoring/channel Idle mode per channel Measured value smoothing Signal range per channel Overflow/underflow monitoring Monitoring to NE43 inputs Monitoring wire break/channel Wire break per channel Limit violation per channel Short circuit/overload per channel parameterisation error Overflow/underflow Limit violation to NE43 per channel Number of HART repetitions Hysteresis for limit values HART variables Behaviour after short circuit/overload |
Polarity protected | for all electrical connections |
Control elements | DIL switches |
LED displays | 1 group diagnostics 4 channel diagnostics 4 channel status |
Repetition accuracy | 0.05% at 25º C |
Protection (short circuit) | Internal electronic fuse protection per channel |
Operating voltage range DC | 18 - 30 V |
Intrinsic current consumption at operating voltage | Typ. 170 mA |
Operating error limit related to the ambient temperature range | ±0,3 % |
Basic error limit at 25°C | ±0,1 % |
Nominal operating voltage DC | 24 V |
Power failure buffering | 10 ms |
Electrical isolation channel – internal bus | Yes |
Electrical isolation channel – channel | No |
CE mark (see declaration of conformity) | to EU directive for EMC |
Vibration resistance | Transport application test at severity level 2 in accordance with FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 2 in accordance with FN 942017-5 and EN 60068-2-27 |
Corrosion resistance classification CRC | 1 - Low corrosion stress (when installed) |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection class | Depending on the connection block |
Ambient temperature | -5 - 50 °C |
Product weight | 77,4 g |
Max. load | 750 Ohm |
Max. input resistance | 300 Ohm |
Max. short circuit current | 22 mA |
Max. open circuit voltage | 28,8 V |
Min. available sensor voltage | 20.7 V at 20 mA |
Signal range | 0 - 20 mA 4 - 20 mA 4 - 20 mA with HART |
Data format | 15 bits + prefix Can be scaled to 15 bit |
Protocol | HART |
Max. line length | 500 m |
Sensor types | 0 - 20 mA 4 - 20 mA 4 - 20 mA with HART |
Mounting type | On interlinking block |
Materials note | Conforms to RoHS |
Material housing | PA-reinforced PC |
© 2020 Festo AG & Co. KG