Festo AG & Co. KG
4080496
bus module
CPX-E-PB
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | 42,2 mm x 125,8 mm x 76,5 mm |
Grid dimension | 18,9 mm |
Diagnostics via LED | Bus error Force mode Power supply electronics/sensors Power supply load System error |
Diagnostics via bus | Wire break Short circuit parameterisation error Overflow buffer Upper limit value not observed Transmission error Lower limit value not observed Undervoltage Watchdog/I/O status Requested function not supported Not ready for data exchange |
Configuration support | Device database file |
Max. no. of modules | 10 |
System parameters | Diagnostic memory Fail-safe reaction Force mode System start |
Module parameters | Undervoltage diagnostics Process value representation of analogue modules |
Control elements | DIL switches |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 75 mA |
Max. power supply | 8 A |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power failure buffering | 20 ms |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Power supply, function | Electronics and sensors |
Power supply, type of connection | Terminal strip |
Power supply, connection technology | Cage clamp terminal |
Power supply, number of pins/wires | 4 |
Power supply, conductor diameter | 0,2 - 1,5 mm2 |
Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Authorisation | RCM Mark |
CE mark (see declaration of conformity) | to EU directive for EMC |
Vibration resistance | Transport application test at severity level 1 in accordance with FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 1 in accordance with FN 942017-5 and EN 60068-2-27 |
Corrosion resistance classification CRC | 0 - No corrosion stress |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection against direct and indirect contact | Protective extra-low voltage with safe disconnection (PELV) |
Protection class | IP20 |
Ambient temperature | -5 - 50 °C |
Note on ambient temperature | -5 - 60°C for vertical installation |
Product weight | 145 g |
Maximum address volume for outputs | 64 Byte |
Note on outputs | 62 bytes with I/O diagnostic interface 64 bytes with status bits 64 bytes without diagnostics |
Maximum address volume for inputs | 64 Byte |
Note on inlets | 62 bytes with I/O diagnostic interface 63 bytes with status bits 64 bytes without diagnostics |
Fieldbus interface, electrical isolation | Yes |
Fieldbus interface, transmission rate | 9,6 kbit/s 19,2 kbit/s 93,75 kbit/s 187,5 kbit/s 500 kbit/s 1,5 Mbit/s 3 Mbit/s 6 Mbit/s 12 Mbit/s |
Fieldbus interface | PROFIBUS |
Fieldbus interface, type of connection | Plug socket |
Fieldbus interface, connection technology | Sub-D |
Fieldbus interface, number of pins/wires | 9 |
Fieldbus interface, protocol | PROFIBUS DP |
Fieldbus interface, max. address volume for inputs | 64 Byte |
Fieldbus interface, max. address volume for outputs | 64 Byte |
Service interface, function | Diagnostics and parameterisation |
Service interface, connection type | Plug socket |
Service interface, connection technology | USB 2.0 type B mini |
Service interface, number of pins/wires | 5 |
Note regarding fieldbus interface | Optional connection technology with accessories: Plug connector/socket M12x1 B-coded, 5-pin, degree of protection IP65 |
Mounting type | with top-hat rail |
Materials note | Contains PWIS substances Conforms to RoHS |
Material housing | PA |
© 2020 Festo AG & Co. KG