Festo AG & Co. KG

4080495
IO-Link master module
CPX-E-4IOL

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H18,9 mm x 76,6 mm x 124,3 mm
Grid dimension18,9 mm
Diagnostics via LEDError per module
Status per channel
Diagnostics via busDevice missing/failed
Wire break
Module error
Short circuit
Parameter error
Overflow/underflow
Undervoltage
General error
Module parametersShort circuit diagnostics for actuator supply
Behaviour after short circuit/overload
Deactivate sensor supply
Channel parametersForce channel x
Deactivate actuator supply
Device error code
Channel mode
Channel status
Cycle time
Protection (short circuit)Internal electronic fuse, load per channel
Internal electronic fuse, sensor for each module
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 50 mA
Intrinsic current consumption at nominal operating voltage loadTypically 15 mA
Nominal operating voltage DC for electronics/sensors24 V
Nominal operating voltage, DC outputs24 V
Electrical isolation channel – internal busNo
Electrical isolation channel – channelNo
Permissible voltage fluctuations for electronics/sensors± 25 %
Permissible voltage fluctuation, outputs± 25 %
Power supply, type of connectionTerminal strip
Power supply, connection technologyCage clamp terminal
Power supply, number of pins/wires4
Power supply, conductor diameter0,2 - 1,5 mm2
Power supply, note on conductor diameter0.2 - 2.5 mm² for flexible conductors without wire end sleeves
AuthorisationRCM Mark
CE mark (see declaration of conformity)to EU directive for EMC
Vibration resistanceTransport application test at severity level 1 in accordance with FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 1 in accordance with FN 942017-5 and EN 60068-2-27
Corrosion resistance classification CRC0 - No corrosion stress
Storage temperature-20 - 70 °C
Relative air humidity95 %
non-condensing
Protection against direct and indirect contactProtective extra-low voltage with safe disconnection (PELV)
Protection classIP20
Ambient temperature-5 - 50 °C
Note on ambient temperature-5 - 50°C for horizontal installation
Product weight96 g
ProtocolIO-Link
IO-Link, protocolMaster V 1.1
IO-Link, communication modeConfigurable via software
SIO, COM1 (4.8 kBaud), COM2 (38.4 kBaud), COM3 (230.4 kBaud)
IO-Link, port typeB
IO-Link, number of ports4
IO-Link, process data width OUTcan be parameterised 8 - 32 byte
IO-Link, process data width INcan be parameterised 8 - 32 byte
IO-Link, minimum cycle timeDependent on minimum supported cycle time of the connected IO-Link® device
IO-Link, communicationC/Q green LED
Electrical connection for IO-Link®, connection type4x terminal strips
Electrical connection for IO-Link®, connection technologyCage clamp terminal
Electrical connection for IO-Link®, number of pins/wires6
Electrical connection for IO-Link®, conductor cross section0,2 - 1,5 mm2
Electrical connection for IO-Link®, note on conductor cross section0.2 - 2.5 mm² for flexible conductors without wire end sleeves
Mounting typewith top-hat rail
Materials noteContains PWIS substances
Conforms to RoHS
Material housingPA

© 2020 Festo AG & Co. KG