Festo AG & Co. KG

3472425
control block
CPX-CEC-S1-V3

Modular controller Codesys V3, Ethernet, serial interfaces.

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H50 mm x 107 mm x 55 mm
Device-specific diagnosticsChannel and module-oriented diagnostics
Undervoltage/short circuit of modules
Diagnostics memory
CPU data256 MB RAM
32 MB Flash
800 MHz processor
Configuration supportCODESYS V3
Parameters configuringCODESYS V3
Additional functionsDiagnostics functions
Communication function RS232
Control elementsRotary switch for run/stop
Programming, operating languageDE, EN
Programming, file handling supportYes
Processing timeApprox. 200 µs/1 k instruction
Data InterfaceRS 232 interface
Sub-D 9-pin, socket
9,6 ... 230,4 kBit/s
Electrically isolated
Intrinsic current consumption at operating voltageTypically 85 mA
IP address selectionDHCP
Via CoDeSys
Via MMI
Functional modulesRead CPX module diagnosis
CPX diagnosis status
Copy CPX diagnosis trace
And others
Flags28 kB retentive data
CoDeSys variable concept
Nominal DC operating voltage, load voltageWithout pneumatics: 18 to 30 V
24 V
With Midi/Maxi type pneumatics: 21.6 to 26.4 V
With CPA type pneumatics: 20.4 to 26.4 V
With MPA type pneumatics: 18 to 30 V
Nominal operating voltage DC24 V
Power failure buffering10 ms
Programming softwareCODESYS provided by Festo
Programming languageTo IEC 61131-3
Ladder diagram (LDR)
Statement list (STL)
Structured text
Function chart
Sequential function chart
Additional CFC
Program memory16 MB user program
Corrosion resistance classification CRC2 - Moderate corrosion stress
Storage temperature-20 - 70 °C
Relative air humidity95 %
non-condensing
Protection classIP65
IP67
Ambient temperature-5 - 50 °C
Product weight135 g
Ethernet, number1
Ethernet, data transmission speed10/100 Mbit/s
Ethernet, supported protocolsTCP/IP, EasyIP, Modbus TCP
Ethernet, connector plugRJ45
Socket
8-pin
ProtocolCODESYS Level 2
EasyIP
Modbus TCP
TCP/IP
Max. line length30 m
Serial interface, number1
Ethernet interfaceRJ 45 (socket, 8-pin)
Bus-specific LED displayTP: Link/Traffic
Product-specific LED displayERR: PLC run-time error
M= modify / forcing active
PL: load supply
PS: Electronics supply, sensor supply
RUN: PLC Status
SF: system error
STOP: PLC status
Materials noteConforms to RoHS
Material housingPA-reinforced
PC

© 2020 Festo AG & Co. KG