Festo AG & Co. KG

573710
analogue module
CPX-4AE-U-I

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H(incl. interlinking block and connection technology)
50 mm x 107 mm x 50 mm
No. of inputs4
DiagnosisWire break per channel
Limit violation per channel
parameterisation error
Overflow/underflow
Overload at input
Short circuit in sensor supply
Parameters configuringData format
Forcing per channel
Limit monitoring/channel
Measured value smoothing
Sensor supply active
Signal range per channel
Behaviour after short circuit
Behaviour after overload at input
Monitoring wire break/channel
LED displays1 group diagnostics
4 channel diagnostics
Internal cycle time500 µs
Repetition accuracy0.1% at 25º C
Protection (short circuit)Internal electronic fuse
Operating voltage range DC18 - 30 V
Intrinsic current consumption at operating voltageTypically 50 mA
Operating error limit related to the ambient temperature range±0,3 %
Basic error limit at 25°C±0,2 %
Nominal DC operating voltage, load voltage24V +/- 2%
Nominal operating voltage DC24 V
Electrical isolation channel – internal busYes, without using the internal sensor supply
Electrical isolation channel – channelNo
Corrosion resistance classification CRC1 - Low corrosion stress
(when installed)
Storage temperature-20 - 70 °C
Protection classDepending on the connection block
Ambient temperature-5 - 50 °C
Product weight46 g
Data format15 bits + prefix
Can be scaled to 15 bit
Max. line length30 m
Shielded
Sensor types+/- 10V
+/- 20mA
+/- 5V
0 - 10 V
0 - 20 mA
1-5 V
4 - 20 mA
Materials noteConforms to RoHS
Material housingPA-reinforced
PC