Festo AG & Co. KG
567347
control block
CPX-CEC-C1
Modular controller Codesys V2.3, Ethernet, CAN.
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | 50 mm x 107 mm x 55 mm |
Device-specific diagnostics | Channel and module-oriented diagnostics Undervoltage/short circuit of modules Diagnostics memory |
CPU data | 32 MB Flash 32 MB RAM 400 MHz processor |
Configuration support | CODESYS V2.3 |
Parameters configuring | CODESYS V2.3 |
Total number of axes | 31 |
Additional functions | Diagnostics functions Motion function for electric drives |
Control elements | DIL switch for CAN terminating plug Rotary switch for run/stop |
Programming, operating language | DE, EN |
Programming, file handling support | Yes |
Baud rate | 10/100 bit/s per IEEE 802.3 (10BaseT) or 802.3u (100BaseTx) |
Processing time | Approx. 200 µs/1 k instruction |
Intrinsic current consumption at operating voltage | Typically 85 mA |
IP address selection | DHCP Via CoDeSys Via MMI |
Functional modules | Read CPX module diagnosis CPX diagnosis status Copy CPX diagnosis trace And others |
Flags | 30 kB retentive data 8 MB global data memory CoDeSys variable concept |
Nominal DC operating voltage, load voltage | Without pneumatics: 18 to 30 V 24 V With Midi/Maxi type pneumatics: 21.6 to 26.4 V With CPA type pneumatics: 20.4 to 26.4 V With MPA type pneumatics: 18 to 30 V |
Nominal operating voltage DC | 24 V |
Power failure buffering | 10 ms |
Programming software | CODESYS provided by Festo V2.3 |
Programming language | To IEC 61131-3 Ladder diagram (LDR) Statement list (STL) Structured text Function chart Sequential function chart Additional CFC |
Program memory | 4 MB user program |
Corrosion resistance classification CRC | 2 - Moderate corrosion stress |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection class | IP65 IP67 |
Ambient temperature | -5 - 50 °C |
Product weight | 155 g |
Ethernet, number | 1 |
Ethernet, data transmission speed | 10/100 Mbit/s |
Ethernet, supported protocols | TCP/IP, EasyIP, Modbus TCP |
Ethernet, connector plug | RJ45 Socket 8-pin |
Fieldbus interface, electrical isolation | Yes |
Fieldbus interface, transmission rate | 125, 250, 500, 800, 1000kbit/s Adjustable via software |
Fieldbus interface, connection technology | Plug Sub-D 9-pin |
Fieldbus interface | CAN-Bus |
Protocol | CODESYS Level 2 EasyIP Modbus TCP TCP/IP |
Control interface | CAN-Bus |
Ethernet interface | RJ 45 (socket, 8-pin) |
Bus-specific LED display | TP: Link/Traffic |
Product-specific LED display | ERR: PLC run-time error M= modify / forcing active PL: load supply PS: Electronics supply, sensor supply RUN: PLC Status SF: system error STOP: PLC status |
Materials note | Conforms to RoHS |
Material housing | PA-reinforced PC |
© 2020 Festo AG & Co. KG