Festo AG & Co. KG
541484
analogue module
CPX-4AE-I
for modular electrical terminal CPX. For sensor signals for pressure, flow rate and distances with current output in a signal range of 4...20 mA.
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | (incl. interlinking block and connection technology) 50 mm x 107 mm x 50 mm |
No. of inputs | 4 |
Diagnosis | Wire break per channel Limit violation per channel Short circuit input signal parameterisation error |
Parameters configuring | Data format Forcing per channel Limit monitoring/channel Measured value smoothing Signal range per channel Behaviour after short circuit Monitoring wire break/channel |
LED displays | 1 group diagnostics |
Internal cycle time | 10 ms |
Repetition accuracy | 0.15% at 25º C |
Protection (short circuit) | Internal electronic fuse |
Operating voltage range DC | 18 - 30 V |
Intrinsic current consumption at operating voltage | Typically 50 mA |
Operating error limit related to the ambient temperature range | ±0,6 % |
Basic error limit at 25°C | ±0,5 % |
Nominal operating voltage DC | 24 V |
Electrical isolation channel – internal bus | Yes, without using the internal sensor supply |
Electrical isolation channel – channel | No |
Corrosion resistance classification CRC | 1 - Low corrosion stress (when installed) |
Storage temperature | -20 - 70 °C |
Protection class | Depending on the connection block |
Ambient temperature | -5 - 50 °C |
Product weight | 47 g |
Data format | 12 bits + prefix Can be scaled to 15 bit |
Max. line length | 30 m Shielded |
Sensor types | 0 - 20 mA 4 - 20 mA |
Material housing | PA-reinforced PC |
© 2020 Festo AG & Co. KG