Festo AG & Co. KG

8086606
analogue input module
CPX-AP-I-4AI-U-I-RTD-M12

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H30 mm x 170 mm x 35 mm
No. of inputs4
Diagnostics via LEDDiagnostics per module
Status per channel
Diagnostics per internal communicationWire break
Module error
Short circuit/overload in sensor supply
Parameter error
parameterisation error
Overload at analogue inputs
Upper limit value not observed
Overflow/underflow
Lower limit value not observed
Polarity protectedYes
Measured variableVoltage
Current
Temperature
Resistor
Repetition accuracy±0.025% at 25 °C
Fuse protection of inputs (short circuit)Internal electronic fuse protection per module
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 38 mA
Operating error limit related to the ambient temperature range±0.15% for voltage
±0.15% for current
±0.35% for resistor
±0.9% for temperature
Basic error limit at 25°C±0.1% for voltage
±0.1% for current
±0.2% for resistor
±0.4% for temperature
Note regarding operating voltageSELV/PELV fixed power supplies required
Note voltage drop
Max. power supply2 x 4 A (external fuse required)
Max. residual current inputs per module1 A
Nominal operating voltage DC for electronics/sensors24 V
Power failure buffering10 ms
Electrical isolation of inputs between channelsNo
Electrical isolation of inputs between channel - internal communicationYes
Permissible voltage fluctuations for electronics/sensors± 25 %
Power supply, functionIncoming electronics/sensors and load
Power supply, type of connectionPlug
Power supply, connection technologyM8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires4
Power transmission, functionOutgoing electronics/sensors and load
Power transmission, connection typePlug socket
Power transmission, connection technologyM8x1, A-coded to EN 61076-2-104
Power transmission, number of pins/wires4
AuthorisationRCM Mark
KC markKC-EMV
CE mark (see declaration of conformity)to EU directive for EMC
UKCA marking (see declaration of conformity)To UK instructions for EMC
Corrosion resistance classification CRC1 - Low corrosion stress
Storage temperature-40 - 70 °C
Relative air humidity5 - 95 %
non-condensing
Protection classIP65
IP67
Note on degree of protectionUnused connections sealed
Ambient temperature-20 - 50 °C
Product weight166 g
Signal range-10 - 10 V
-5 - 5 V
0 - 10 V
0 - 20 mA
0 - 500 ohm
1 - 5 V
4 - 20 mA
Data format15 bits + prefix
Linear scaling
Max. line length30 m inputs
50 m system communication
Communication interface, functionSystem communication XF10 IN / XF20 OUT
Communication interface, connection type2x socket
Communication interface, connection technologyM8x1, D-coded to EN 61076-2-114
Communication interface, number of pins/wires4
Communication interface, protocolAP-COM
Communication interface, screeningYes
Electrical connection, input, functionAnalogue input
Electrical connection, input, connection type4x socket
Electrical connection, input, connection technologyM12x1, A-coded in accordance with EN 61076-2-101
Electrical connection, input, note on connection technologyTo achieve the technical specifications, the opposite side must be screened and designed with gold contact surfaces.
Electrical connection, input, number of pins/wires5
Mounting typeOn H-rail with accessories
with through hole
Materials noteConforms to RoHS
Material sealsNBR
Material housingPA
PC
Nickel-plated die-cast zinc
Material o-ringFPM

© 2022 Festo AG & Co. KG