Festo AG & Co. KG
8086604
IO-Link Master
CPX-AP-I-4IOL-M12
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | 30 mm x 170 mm x 35 mm |
Diagnostics via LED | Diagnostics per channel Diagnostics per module Power supply load Status per channel Status per module |
Diagnostics per internal communication | IO-Link® event Short circuit/overload in sensor supply Electronics/sensors overvoltage Load overvoltage Electronics/sensors undervoltage Load undervoltage |
Polarity protected | Yes |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 55 mA |
Intrinsic current consumption at nominal operating voltage load | Typical 5 mA |
Note regarding operating voltage | SELV/PELV fixed power supplies required Note voltage drop |
Max. power supply | 2 x 4 A (external fuse required) |
Nominal operating voltage DC for electronics/sensors | 24 V |
Nominal operating voltage, DC outputs | 24 V |
Power failure buffering | 10 ms |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Permissible voltage fluctuations, load | ± 25 % |
Power supply, function | Incoming electronics/sensors and load |
Power supply, type of connection | Plug |
Power supply, connection technology | M8x1, A-coded to EN 61076-2-104 |
Power supply, number of pins/wires | 4 |
Power transmission, function | Outgoing electronics/sensors and load |
Power transmission, connection type | Plug socket |
Power transmission, connection technology | M8x1, A-coded to EN 61076-2-104 |
Power transmission, number of pins/wires | 4 |
Authorisation | RCM Mark |
KC mark | KC-EMV |
CE mark (see declaration of conformity) | to EU directive for EMC |
UKCA marking (see declaration of conformity) | To UK instructions for EMC |
Corrosion resistance classification CRC | 1 - Low corrosion stress |
Storage temperature | -40 - 70 °C |
Relative air humidity | 5 - 95 % non-condensing |
Protection class | IP65 IP67 |
Note on degree of protection | Unused connections sealed |
Ambient temperature | -20 - 50 °C |
Product weight | 126 g |
Protocol | IO-Link |
IO-Link, protocol | Master V 1.1 |
IO-Link, communication mode | Configurable via software SIO, COM1 (4.8 kBaud), COM2 (38.4 kBaud), COM3 (230.4 kBaud) |
IO-Link, port type | B |
IO-Link, number of ports | 4 |
IO-Link, process data width OUT | Can be parameterised 8 - 128 bytes |
IO-Link, process data width IN | Can be parameterised 12 - 132 bytes |
IO-Link, minimum cycle time | Dependent on minimum supported cycle time of the connected IO-Link® device |
Max. line length | 20 m with IO-Link operation 50 m system communication |
IO-Link, communication | C/Q green LED |
Communication interface, function | System communication XF10 IN / XF20 OUT |
Communication interface, connection type | 2x socket |
Communication interface, connection technology | M8x1, D-coded to EN 61076-2-114 |
Communication interface, number of pins/wires | 4 |
Communication interface, protocol | AP-COM |
Communication interface, screening | Yes |
Electrical connection for IO-Link®, connection type | 4x socket |
Electrical connection for IO-Link®, connection technology | M12x1, A-coded in accordance with EN 61076-2-101 |
Electrical connection for IO-Link®, number of pins/wires | 5 |
Mounting type | On H-rail with accessories with through hole |
Materials note | Conforms to RoHS |
Material housing | PA PC Nickel-plated die-cast zinc |
Material o-ring | FPM |