Festo AG & Co. KG

8086604
IO-Link Master
CPX-AP-I-4IOL-M12

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H30 mm x 170 mm x 35 mm
Diagnostics via LEDDiagnostics per channel
Diagnostics per module
Power supply load
Status per channel
Status per module
Diagnostics per internal communicationIO-Link® event
Short circuit/overload in sensor supply
Electronics/sensors overvoltage
Load overvoltage
Electronics/sensors undervoltage
Load undervoltage
Polarity protectedYes
Intrinsic current consumption at nominal operating voltage for electronics/sensorsTypically 55 mA
Intrinsic current consumption at nominal operating voltage loadTypical 5 mA
Note regarding operating voltageSELV/PELV fixed power supplies required
Note voltage drop
Max. power supply2 x 4 A (external fuse required)
Nominal operating voltage DC for electronics/sensors24 V
Nominal operating voltage, DC outputs24 V
Power failure buffering10 ms
Permissible voltage fluctuations for electronics/sensors± 25 %
Permissible voltage fluctuations, load± 25 %
Power supply, functionIncoming electronics/sensors and load
Power supply, type of connectionPlug
Power supply, connection technologyM8x1, A-coded to EN 61076-2-104
Power supply, number of pins/wires4
Power transmission, functionOutgoing electronics/sensors and load
Power transmission, connection typePlug socket
Power transmission, connection technologyM8x1, A-coded to EN 61076-2-104
Power transmission, number of pins/wires4
AuthorisationRCM Mark
KC markKC-EMV
CE mark (see declaration of conformity)to EU directive for EMC
UKCA marking (see declaration of conformity)To UK instructions for EMC
Corrosion resistance classification CRC1 - Low corrosion stress
Storage temperature-40 - 70 °C
Relative air humidity5 - 95 %
non-condensing
Protection classIP65
IP67
Note on degree of protectionUnused connections sealed
Ambient temperature-20 - 50 °C
Product weight126 g
ProtocolIO-Link
IO-Link, protocolMaster V 1.1
IO-Link, communication modeConfigurable via software
SIO, COM1 (4.8 kBaud), COM2 (38.4 kBaud), COM3 (230.4 kBaud)
IO-Link, port typeB
IO-Link, number of ports4
IO-Link, process data width OUTCan be parameterised 8 - 128 bytes
IO-Link, process data width INCan be parameterised 12 - 132 bytes
IO-Link, minimum cycle timeDependent on minimum supported cycle time of the connected IO-Link® device
Max. line length20 m with IO-Link operation
50 m system communication
IO-Link, communicationC/Q green LED
Communication interface, functionSystem communication XF10 IN / XF20 OUT
Communication interface, connection type2x socket
Communication interface, connection technologyM8x1, D-coded to EN 61076-2-114
Communication interface, number of pins/wires4
Communication interface, protocolAP-COM
Communication interface, screeningYes
Electrical connection for IO-Link®, connection type4x socket
Electrical connection for IO-Link®, connection technologyM12x1, A-coded in accordance with EN 61076-2-101
Electrical connection for IO-Link®, number of pins/wires5
Mounting typeOn H-rail with accessories
with through hole
Materials noteConforms to RoHS
Material housingPA
PC
Nickel-plated die-cast zinc
Material o-ringFPM

© 2022 Festo AG & Co. KG