Festo AG & Co. KG

8059847
input module
CPX-4AE-4AA-H

HART-capable, configurable as input or output.

More detailed information about this product!

Festo Data sheet

CriterionFeature
Dimensions W x L x H(incl. interlinking block and connection technology)
50 mm x 107 mm x 70 mm
Grid dimension50 mm
Number of selectable analogue inputs/outputs4
DiagnosisWire break per channel
Limit violation per channel
Limit violation to NE43 per channel
Short circuit/overload per channel
parameterisation error
Overflow/underflow
Parameters configuringData format
Fail-safe mode per channel
Forcing per channel
Limit monitoring/channel
Idle mode per channel
Measured value smoothing
Signal range per channel
Overflow/underflow monitoring
Monitoring to NE43 inputs
Monitoring wire break/channel
Wire break per channel
Limit violation per channel
Short circuit/overload per channel
parameterisation error
Overflow/underflow
Limit violation to NE43 per channel
Number of HART repetitions
Hysteresis for limit values
HART variables
Behaviour after short circuit/overload
Polarity protectedfor all electrical connections
Control elementsDIL switches
LED displays1 group diagnostics
4 channel diagnostics
4 channel status
Repetition accuracy0.05% at 25º C
Protection (short circuit)Internal electronic fuse protection per channel
Operating voltage range DC18 - 30 V
Intrinsic current consumption at operating voltageTyp. 170 mA
Operating error limit related to the ambient temperature range±0,3 %
Basic error limit at 25°C±0,1 %
Nominal operating voltage DC24 V
Power failure buffering10 ms
Electrical isolation channel – internal busYes
Electrical isolation channel – channelNo
CE mark (see declaration of conformity)to EU directive for EMC
Vibration resistanceTransport application test at severity level 2 in accordance with FN 942017-4 and EN 60068-2-6
Shock resistanceShock test with severity level 2 in accordance with FN 942017-5 and EN 60068-2-27
Corrosion resistance classification CRC1 - Low corrosion stress
(when installed)
Storage temperature-20 - 70 °C
Relative air humidity95 %
non-condensing
Protection classDepending on the connection block
Ambient temperature-5 - 50 °C
Product weight77,4 g
Max. load750 Ohm
Max. input resistance300 Ohm
Max. short circuit current22 mA
Max. open circuit voltage28,8 V
Min. available sensor voltage20.7 V at 20 mA
Signal range0 - 20 mA
4 - 20 mA
4 - 20 mA with HART
Data format15 bits + prefix
Can be scaled to 15 bit
ProtocolHART
Max. line length500 m
Sensor types0 - 20 mA
4 - 20 mA
4 - 20 mA with HART
Mounting typeOn interlinking block
Materials noteConforms to RoHS
Material housingPA-reinforced
PC

© 2022 Festo AG & Co. KG