Festo AG & Co. KG
4827505
counter module
CPX-E-1CI
More detailed information about this product!
Festo Data sheet
Criterion | Feature |
Dimensions W x L x H | 18,9 mm x 76,6 mm x 124,3 mm |
Grid dimension | 18,9 mm |
No. of inputs | 4 |
Diagnostics via LED | Encoder supply error Error per module Encoder error Encoder normal operation Encoder supply normal operation Status per channel |
Diagnostics via bus | Measuring system error Short circuit/overload in sensor supply Parameter error Monitoring of wire break Monitoring of zero pulse Monitoring of tracking error |
Module parameters | Signal type/encoder type Signal evaluation Monitoring of cable break Monitoring of tracking error Monitoring of zero pulse Pulse/zero pulse Latch signal Latch event Latch response Upper count limit Lower count limit Load value Debounce time for digital inputs Integration time for speed measurement Internal Revision ID |
Channel parameters | Signal extension |
Input debounce time | 0,02 ms 0,1 ms 3 ms |
Protection (short circuit) | Internal electronic fuse protection per module |
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 15 mA |
Max. residual current inputs per module | 1,8 A |
Nominal operating voltage DC for electronics/sensors | 24 V |
Power failure buffering | 10 ms |
Electrical isolation channel – internal bus | No |
Electrical isolation channel – channel | No |
Switching level | Signal 0: <= 5 V Signal 1: >= 11 V |
Permissible voltage fluctuations for electronics/sensors | ± 25 % |
Power supply, function | Encoder supply |
Power supply, type of connection | Terminal strip |
Power supply, connection technology | Cage clamp terminal |
Power supply, number of pins/wires | 6 |
Power supply, conductor diameter | 0,2 - 1,5 mm2 |
Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Authorisation | RCM Mark c UL us - Listed (OL) |
KC mark | KC-EMV |
CE mark (see declaration of conformity) | to EU directive for EMC |
Certificate issuing department | UL E239998 |
Vibration resistance | Transport application test at severity level 1 in accordance with FN 942017-4 and EN 60068-2-6 |
Shock resistance | Shock test with severity level 1 in accordance with FN 942017-5 and EN 60068-2-27 |
Corrosion resistance classification CRC | 0 - No corrosion stress |
Storage temperature | -20 - 70 °C |
Relative air humidity | 95 % non-condensing |
Protection class | IP20 |
Ambient temperature | -5 - 50 °C |
Note on ambient temperature | -5 - 60°C for vertical installation |
Product weight | 88 g |
Maximum address volume for outputs | 2 Byte |
Maximum address volume for inputs | 12 Byte |
Input characteristics | to IEC 61131-2, type 3 |
Input circuit logic | PNP (positive-switching) 2-wire sensors to IEC 61131-2 3-wire sensors to IEC 61131-2 |
Electrical connection, input, function | Digitaleingang |
Electrical connection, input, connection type | 2x terminal strips |
Electrical connection, input, connection technology | Cage clamp terminal |
Electrical connection, input, number of pins/wires | 6 |
Electrical connection for input, conductor cross section | 0,2 - 1,5 mm2 |
Electrical connection for input, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Electrical connection for input 2, function | Counter input |
Electrical connection for input 2, connection type | Terminal strip |
Electrical connection for input 2, connection technology | Cage clamp terminal |
Electrical connection for input 2, number of pins/wires | 6 |
Electrical connection for input 2, connection pattern | 00995848 |
Electrical connection for input 2, conductor cross section | 0,2 - 1,5 mm2 |
Electrical connection for input 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves |
Mounting type | with top-hat rail |
Materials note | Contains PWIS substances Conforms to RoHS |
Material housing | PA |
© 2022 Festo AG & Co. KG